ATS48M10Y
Schneider Electric
Product Lifecycle: Active
SOFT START 208-690VAC 1000A ATS48
SOFT START 208-690VAC 1000A ATS48
Product details
- Maximum Horse Power Rating1000 hp 575 V for standard applications 250 hp 208 V for severe applications 300 hp 230 V for severe applications 350 hp 208 V for standard applications 350 hp 230 V for standard applications 600 hp 460 V for severe applications<b
- Motor Power Kw220 kW 230 V for severe applications 250 kW 230 V for standard applications 400 kW 400 V for severe applications 500 kW 400 V for standard applications 500 kW 440 V for severe applications 500 kW 500 V for severe applications<br /
- Motor Power Range AC-3110…220 kW 200…240 V 3 phase 250…500 kW 380…440 V 3 phase 250…500 kW 480…500 V 3 phase 250…500 kW 200…240 V 3 phase 560…900 kW 380…440 V 3 phase 560…900 kW 480…500 V 3 phase
- Protection TypePhase failure line Thermal protection motor Thermal protection starter
- Maximum Switching CurrentLogic output 0.2 A 30 V DC Relay outputs 1.8 A 230 V AC inductive, cos phi = 0.5 20 ms Relay outputs 1.8 A 30 V DC inductive, cos phi = 0.5 20 ms
- Discrete Output TypeLO1) logic output 0 V common configurable LO2) logic output 0 V common configurable R1) relay outputs fault relay NO R2) relay outputs end of starting relay NO R3) relay outputs motor powered NO
- Power Dissipation In W2225 W for standard applications 2865 W for standard applications
- Icl Nominal Current1000 A connection in the motor supply line for standard applications 1000 A connection in the motor supply line for severe applications
- Discrete Input TypePTC, 750 Ohm 77 °F (25 °C) Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
- Height35.04 in (890 mm)
- Starting Current0.4...1.3 Icl adjustable
- Minimum Switching Current10 mA 6 V DC relay outputs
- Motor Starter TypeSoft starter
- Net Weight253.53 lb(US) (115 kg)
- Depth12.40 in (315 mm)
- Transmission Rate4800, 9600 or 19200 bps
- Width30.31 in (770 mm)
- Operating PositionVertical +/- 10 degree
- MarkingCE
- Max Nodes Number31
- Discrete Input Number5
- Physical InterfaceRS485 multidrop
- Communication Data LinkSerial
- Discrete Input Voltage24 V <= 30 V
- Discrete Input LogicPositive logic Stop, Run, LI3, LI4 < 5 V <= 2 mA > 11 V, >= 5 mA
- Connector Type1 RJ45
- Communication Port ProtocolModbus
- Analogue Output TypeCurrent output AO 0-20 mA or 4-20 mA 500 Ohm
- Discrete Output Number2
- Output Absolute Accuracy Precision+/- 5 %
- Utilisation CategoryAC-53A
- Device ConnectionIn the motor supply line
- Power Supply Frequency Limits47.5...63 Hz
- Power Supply Frequency50...60 Hz - 5...5 %
- Function AvailableExternal bypass (optional)
- Assembly StyleWith heat sink
- Type Of StartStart with torque control (current limited to 5 In)
- Device Short NameATS48
- Power Supply Voltage208...690 V - 15...10 %
- Product Specific ApplicationHeavy duty industry and pumps
- Product Or Component TypeSoft starter
- Product DestinationAsynchronous motors
- Range Of ProductAltistart 48
Get a quick quote
Select Qty:
Average response time:
11 minutes
This part can ship within 24h!
Fast worldwide Shipping and Delivery
Shipping cost will be calculated during checkout
Payments methods
Secure Payment Processing
with money back guarantee
1 year warranty on all parts
Responsive Customer Support
with personalized assistance
Need more details?
Feel free to chat with us.