LC1D65ABD

Schneider Electric

Product Lifecycle: Active

IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style

LC1D65ABD

IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style

  • [Icw] Rated Short-Time Withstand Current520 A 104 °F (40 °C) - 10 s power circuit 900 A 104 °F (40 °C) - 1 s power circuit 110 A 104 °F (40 °C) - 10 min power circuit 260 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling cir
  • Motor Power HP (UL / CSA)40 hp 460/480 V at AC 50/60 Hz for 3 phase 5 hp 115 V at AC 50/60 Hz for 1 phase 10 hp 230/240 V at AC 50/60 Hz for 1 phase 20 hp 200/208 V at AC 50/60 Hz for 3 phase 20 hp 230/240 V at AC 50/60 Hz for 3 phase 50 hp 575/600 V at A
  • [Ui] Rated Insulation VoltagePower circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL Power circuit 690 V IEC 60947-4-1
  • StandardsCSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
  • Motor Power Kw11 kW 400 V AC 50/60 Hz AC-4) 18.5 kW 220...230 V AC 50/60 Hz AC-3) 30 kW 380...400 V AC 50/60 Hz AC-3) 37 kW 500 V AC 50/60 Hz AC-3) 37 kW 660...690 V AC 50/60 Hz AC-3)
  • Product CertificationsGOST UL CCC CSA
  • Connections - TerminalsControl circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)fle
  • Control Circuit Voltage Limits0.1...0.3 Uc -40…158 °F (-40…70 °C) drop-out DC 0.75...1.25 Uc -40…140 °F (-40…60 °C) operational DC 1...1.25 Uc 140…158 °F (60…70 °C) operational DC
  • Tightening TorqueControl circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 70.81 lbf.in (8 N.m) EverLink BTR screw connectors 0.04…0.05 in² (25…35 mm²) hexagon
  • Irms Rated Making Capacity140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 1000 A 440 V power circuit IEC 60947
  • Associated Fuse Rating10 A gG signalling circuit IEC 60947-5-1 125 A gG <= 690 V type 1 power circuit 125 A gG <= 690 V type 2 power circuit
  • Utilisation CategoryAC-3 AC-4 AC-1
  • Auxiliary Contacts TypeMechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
  • [Ith] Conventional Free Air Thermal Current10 A 140 °F (60 °C) signalling circuit 80 A 140 °F (60 °C) power circuit
  • Electrical Durability0.5 Mcycles 80 A AC-1 <= 440 V 1.45 Mcycles 65 A AC-3 <= 440 V
  • Operating Time42.5...57.5 ms closing 16...24 ms opening
  • Mounting SupportPlate Rail
  • Non-Overlap Time1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
  • [Ie] Rated Operational Current80 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit 65 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
  • [Ue] Rated Operational VoltagePower circuit <= 690 V AC 25...400 Hz Power circuit <= 300 V DC
  • Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Power Dissipation Per Pole9.6 W AC-1 6.3 W AC-3
  • Contactor ApplicationMotor control Resistive load
  • Signalling Circuit Frequency25...400 Hz
  • Insulation Resistance> 10 MOhm signalling circuit
  • Coil TechnologyBuilt-in bidirectional peak limiting diode suppressor
  • Inrush Power In W19 W 68 °F (20 °C))
  • Minimum Switching Voltage17 V signalling circuit
  • Minimum Switching Current5 mA signalling circuit
  • Hold-In Power Consumption In W7.4 W 68 °F (20 °C)
  • Time Constant34 ms
  • Maximum Operating Rate3600 cyc/h 140 °F (60 °C)
  • Mechanical Durability10 Mcycles
  • Front CoverWith
  • Average Impedance1.5 mOhm - Ith 80 A 50 Hz power circuit
  • Rated Breaking Capacity1000 A 440 V power circuit IEC 60947
  • Product NameTeSys D
  • Overvoltage CategoryIII
  • [Uimp] Rated Impulse Withstand Voltage6 kV IEC 60947
  • Auxiliary Contact Composition1 NO + 1 NC
  • Product Or Component TypeContactor
  • RangeTeSys
  • [Uc] Control Circuit Voltage24 V DC
  • Device Short NameLC1D
  • Power Pole Contact Composition3 NO
  • Control Circuit TypeDC standard
  • Poles Description3P
This part can ship within 24 hours
Support Agent Icon

$403.00

Stock:

1

Select Qty:

$403.00

$403.00 each

This part can ship within 24h!

Fast worldwide Shipping and Delivery

Shipping cost will be calculated during checkout


Payments methods

Secure Payment Processing
with money back guarantee

1 year warranty on all parts


Responsive Customer Support
with personalized assistance


Need more details?

Feel free to chat with us.

Friendly Powermatic robot

What can I help you find today?