LC1D95Q7
Schneider Electric
Product Lifecycle: Active
IEC contactor, TeSys Deca, nonreversing, 95A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 380VAC 50/60Hz coil, open style
IEC contactor, TeSys Deca, nonreversing, 95A, 60HP at 480VAC, 3 phase, 3 pole, 3 NO, 380VAC 50/60Hz coil, open style
Product details
- Product CertificationsIECEE CB Scheme UL CSA CCC EAC LROS (Lloyds register of shipping) RINA BV DNV-GL
- StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4
- [Icw] Rated Short-Time Withstand Current1100 A 104 °F (40 °C) - 1 s power circuit 800 A 104 °F (40 °C) - 10 s power circuit 400 A 104 °F (40 °C) - 1 min power circuit 135 A 104 °F (40 °C) - 10 min power circuit 140 A - 100 ms signalling circuit 120 A - 500 ms signalling
- Motor Power HP (UL / CSA)7.5 hp 115 V at AC 60 Hz for 1 phase 15 hp 230/240 V at AC 60 Hz for 1 phase 25 hp 200/208 V at AC 60 Hz for 3 phase 30 hp 230/240 V at AC 60 Hz for 3 phase 60 hp 460/480 V at AC 60 Hz for 3 phase 60 hp 575/600 V at AC 60 Hz for 3
- Motor Power Kw25 kW 220...230 V AC 50 Hz AC-3) 45 kW 380...400 V AC 50 Hz AC-3) 45 kW 415...440 V AC 50 Hz AC-3) 55 kW 500 V AC 50 Hz AC-3) 45 kW 660...690 V AC 50 Hz AC-3) 45 kW 1000 V AC 50 Hz AC-3)
- [Ui] Rated Insulation VoltagePower circuit 1000 V IEC 60947-4-1 Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL
- Tightening TorqueControl circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals Philips No 2 Power circuit 106.21 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm Power circuit 106.21 lbf.in
- Control Circuit Voltage Limits0.8...1.1 Uc -40…131 °F (-40…55 °C) operational AC 50 Hz 0.85...1.1 Uc -40…131 °F (-40…55 °C) operational AC 60 Hz 0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz 1...1.1 Uc 131…158 °F (55…70 °C) operational AC 50/60 Hz
- Associated Fuse Rating10 A gG signalling circuit IEC 60947-5-1 200 A gG <= 690 V type 1 power circuit 160 A gG <= 690 V type 2 power circuit
- Connections - TerminalsControl circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flex
- Irms Rated Making Capacity1100 A 440 V AC power circuit IEC 60947 140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1
- Utilisation CategoryAC-3 AC-4 AC-1
- Non-Overlap Time1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
- Auxiliary Contacts TypeMechanically linked 1 NO + 1 NC IEC 60947-5-1 Mirror contact 1 NC IEC 60947-4-1
- Safety Reliability LevelB10d = 1.3 Mcycles contactor with nominal load EN/ISO 13849-1 B10d = 20 Mcycles contactor with mechanical load EN/ISO 13849-1
- Electrical Durability1.2 Mcycles 95 A AC-3 1.3 Mcycles 125 A AC-1
- Operating Time20...35 ms closing 6...20 ms opening
- Inrush Power In VA245 VA 60 Hz 0.75 68 °F (20 °C)) 245 VA 50 Hz 0.75 68 °F (20 °C))
- [Ie] Rated Operational Current95 A 140 °F (60 °C)) <= 440 V AC-3 power circuit 125 A 140 °F (60 °C)) <= 690 V AC-1 power circuit
- Hold-In Power Consumption In VA26 VA 60 Hz 0.3 68 °F (20 °C)) 26 VA 50 Hz 0.3 68 °F (20 °C))
- Mounting SupportRail Plate
- Contactor ApplicationResistive load Motor control
- Power Dissipation Per Pole12.5 W AC-1 7.2 W AC-3
- [Ith] Conventional Free Air Thermal Current10 A 140 °F (60 °C) signalling circuit 125 A 140 °F (60 °C) power circuit
- Signalling Circuit Frequency25...400 Hz
- Coil TechnologyWithout built-in suppressor module
- Insulation Resistance> 10 MOhm signalling circuit
- Minimum Switching Current5 mA signalling circuit
- Minimum Switching Voltage17 V signalling circuit
- Heat Dissipation6…10 W 50/60 Hz
- Maximum Operating Rate3600 cyc/h 140 °F (60 °C)
- Mechanical Durability4 Mcycles
- Front CoverWith
- Average Impedance0.8 mOhm - Ith 125 A 50 Hz power circuit
- Rated Breaking Capacity1100 A 440 V power circuit IEC 60947
- Overvoltage CategoryIII
- [Uimp] Rated Impulse Withstand Voltage8 kV IEC 60947
- Auxiliary Contact Composition1 NO + 1 NC
- [Uc] Control Circuit Voltage380 V AC 50/60 Hz
- Control Circuit TypeAC 50/60 Hz
- [Ue] Rated Operational VoltagePower circuit 1000 V AC 25...400 Hz
- Product NameTeSys D
- Poles Description3P
- Power Pole Contact Composition3 NO
- Device Short NameLC1D
- Product Or Component TypeContactor
- RangeTeSys
Get a quick quote
Select Qty:
Average response time:
11 minutes
This part can ship within 24h!
Fast worldwide Shipping and Delivery
Shipping cost will be calculated during checkout
Payments methods
Secure Payment Processing
with money back guarantee
1 year warranty on all parts
Responsive Customer Support
with personalized assistance
Need more details?
Feel free to chat with us.