LC1F265X7

Schneider Electric

Product Lifecycle: Active

contactor, TeSys F, 3P(3NO), AC-3, <=440V 265 A, coil 550...600V AC

LC1F265X7

contactor, TeSys F, 3P(3NO), AC-3, <=440V 265 A, coil 550...600V AC

  • Product CertificationsCCC RINA CB BV RMRoS UL DNV LROS (Lloyds register of shipping) ABS UKCA
  • Motor Power Kw132 kW 380...400 V AC 50/60 Hz AC-3) 140 kW 415 V AC 50/60 Hz AC-3) 140 kW 440 V AC 50/60 Hz AC-3) 160 kW 500 V AC 50/60 Hz AC-3) 160 kW 660...690 V AC 50/60 Hz AC-3) 147 kW 1000 V AC 50/60 Hz AC-3) 75 kW 220...230 V AC 50/60
  • [Icw] Rated Short-Time Withstand Current2200 A 104 °F (40 °C) - 10 s 1230 A 104 °F (40 °C) - 30 s 950 A 104 °F (40 °C) - 1 min 620 A 104 °F (40 °C) - 3 min 480 A 104 °F (40 °C) - 10 min
  • StandardsEN 60947-1 IEC 60947-1 JIS C8201-4-1 IEC 60947-4-1 EN 60947-4-1
  • Connections - TerminalsControl circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)fl
  • Utilisation CategoryAC-4 AC-1 AC-3
  • Associated Fuse Rating315 A aM <= 440 V 400 A gG <= 440 V
  • Operating Time40...65 ms closing 100...170 ms opening
  • Control Circuit Voltage LimitsOperational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.15...0.2 Uc 40...400 Hz 131 °F (55 °C))
  • [Ui] Rated Insulation Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
  • Tightening TorqueControl circuit 10.62 lbf.in (1.2 N.m) Power circuit 309.78 lbf.in (35 N.m)
  • [Ue] Rated Operational Voltage<= 1000 V AC 50/60 Hz <= 460 V DC
  • Power Dissipation Per Pole37 W AC-1 21 W AC-3
  • Contactor ApplicationMotor control Resistive load
  • [Ie] Rated Operational Current350 A 104 °F (40 °C)) <= 440 V AC AC-1 265 A 131 °F (55 °C)) <= 440 V AC AC-3
  • Mechanical Durability10 Mcycles
  • Compatibility CodeLC1F
  • Hold-In Power Consumption In VA10 VA 40...400 Hz 0.9 68 °F (20 °C))
  • [Uc] Control Circuit Voltage550...600 V AC 40...400 Hz
  • Product NameTeSys F
  • Maximum Operating Rate2400 cyc/h 131 °F (55 °C)
  • Heat Dissipation8 W
  • Inrush Power In VA650 VA 40...400 Hz 0.9 68 °F (20 °C))
  • Mounting SupportPlate
  • Average Impedance0.3 mOhm - Ith 350 A 50 Hz
  • [Uimp] Rated Impulse Withstand Voltage8 kV
  • Rated Breaking Capacity2120 A IEC 60947-4-1
  • [Ith] Conventional Free Air Thermal Current350 A 104 °F (40 °C)
  • Overvoltage CategoryIII
  • RangeTeSys
  • Poles Description3P
  • Power Pole Contact Composition3 NO
  • Product Or Component TypeContactor
  • Device Short NameLC1F

Get a quick quote

Select Qty:

Average response time:

11 minutes

This part can ship within 24h!

Fast worldwide Shipping and Delivery

Shipping cost will be calculated during checkout


Payments methods

Secure Payment Processing
with money back guarantee

1 year warranty on all parts


Responsive Customer Support
with personalized assistance


Need more details?

Feel free to chat with us.

Relevant products

Friendly Powermatic robot

What can I help you find today?