LC1F265X7
Schneider Electric
Product Lifecycle: Active
contactor, TeSys F, 3P(3NO), AC-3, <=440V 265 A, coil 550...600V AC
contactor, TeSys F, 3P(3NO), AC-3, <=440V 265 A, coil 550...600V AC
Product details
- Product CertificationsCCC RINA CB BV RMRoS UL DNV LROS (Lloyds register of shipping) ABS UKCA
- Motor Power Kw132 kW 380...400 V AC 50/60 Hz AC-3) 140 kW 415 V AC 50/60 Hz AC-3) 140 kW 440 V AC 50/60 Hz AC-3) 160 kW 500 V AC 50/60 Hz AC-3) 160 kW 660...690 V AC 50/60 Hz AC-3) 147 kW 1000 V AC 50/60 Hz AC-3) 75 kW 220...230 V AC 50/60
- [Icw] Rated Short-Time Withstand Current2200 A 104 °F (40 °C) - 10 s 1230 A 104 °F (40 °C) - 30 s 950 A 104 °F (40 °C) - 1 min 620 A 104 °F (40 °C) - 3 min 480 A 104 °F (40 °C) - 10 min
- StandardsEN 60947-1 IEC 60947-1 JIS C8201-4-1 IEC 60947-4-1 EN 60947-4-1
- Connections - TerminalsControl circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)fl
- Utilisation CategoryAC-4 AC-1 AC-3
- Associated Fuse Rating315 A aM <= 440 V 400 A gG <= 440 V
- Operating Time40...65 ms closing 100...170 ms opening
- Control Circuit Voltage LimitsOperational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.15...0.2 Uc 40...400 Hz 131 °F (55 °C))
- [Ui] Rated Insulation Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
- Tightening TorqueControl circuit 10.62 lbf.in (1.2 N.m) Power circuit 309.78 lbf.in (35 N.m)
- [Ue] Rated Operational Voltage<= 1000 V AC 50/60 Hz <= 460 V DC
- Power Dissipation Per Pole37 W AC-1 21 W AC-3
- Contactor ApplicationMotor control Resistive load
- [Ie] Rated Operational Current350 A 104 °F (40 °C)) <= 440 V AC AC-1 265 A 131 °F (55 °C)) <= 440 V AC AC-3
- Mechanical Durability10 Mcycles
- Compatibility CodeLC1F
- Hold-In Power Consumption In VA10 VA 40...400 Hz 0.9 68 °F (20 °C))
- [Uc] Control Circuit Voltage550...600 V AC 40...400 Hz
- Product NameTeSys F
- Maximum Operating Rate2400 cyc/h 131 °F (55 °C)
- Heat Dissipation8 W
- Inrush Power In VA650 VA 40...400 Hz 0.9 68 °F (20 °C))
- Mounting SupportPlate
- Average Impedance0.3 mOhm - Ith 350 A 50 Hz
- [Uimp] Rated Impulse Withstand Voltage8 kV
- Rated Breaking Capacity2120 A IEC 60947-4-1
- [Ith] Conventional Free Air Thermal Current350 A 104 °F (40 °C)
- Overvoltage CategoryIII
- RangeTeSys
- Poles Description3P
- Power Pole Contact Composition3 NO
- Product Or Component TypeContactor
- Device Short NameLC1F
Get a quick quote
Select Qty:
Average response time:
11 minutes
This part can ship within 24h!
Fast worldwide Shipping and Delivery
Shipping cost will be calculated during checkout
Payments methods
Secure Payment Processing
with money back guarantee
1 year warranty on all parts
Responsive Customer Support
with personalized assistance
Need more details?
Feel free to chat with us.