LC1F400FD
Schneider Electric
Product Lifecycle: Active
FR catalog.xlsx - SM-618
FR catalog.xlsx - SM-618
Product details
- Product CertificationsUL CSA CB ABS BV DNV LROS (Lloyds register of shipping) RMRoS RINA UKCA
- Motor Power Kw75 kW 400 V AC 50/60 Hz AC-4) 200 kW 380...400 V AC 50/60 Hz AC-3) 220 kW 415 V AC 50/60 Hz AC-3) 250 kW 440 V AC 50/60 Hz AC-3) 257 kW 500 V AC 50/60 Hz AC-3) 280 kW 660...690 V AC 50/60 Hz AC-3) 185 kW 1000 V AC 50/60 Hz AC
- StandardsIEC 60947-4-1 JIS C8201-4-1 EN 60947-4-1 EN 60947-1 IEC 60947-1
- [Icw] Rated Short-Time Withstand Current3600 A 104 °F (40 °C) - 10 s 2400 A 104 °F (40 °C) - 30 s 1700 A 104 °F (40 °C) - 1 min 1200 A 104 °F (40 °C) - 3 min 1000 A 104 °F (40 °C) - 10 min
- Motor Power Range110…220 kW 480…500 V 3 phase 110…220 kW 380…440 V 3 phase 110…220 kW 200…240 V 3 phase 250…500 kW 480…500 V 3 phase
- Utilisation CategoryAC-3 AC-1 AC-4
- Connections - TerminalsControl circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)fl
- [Ie] Rated Operational Current500 A 104 °F (40 °C)) <= 440 V AC AC-1 400 A 131 °F (55 °C)) <= 440 V AC AC-3
- Power Dissipation Per Pole65 W AC-1 42 W AC-3
- Operating Time50...60 ms closing 45...60 ms opening
- Associated Fuse Rating400 A aM <= 440 V 500 A gG <= 440 V
- Control Circuit Voltage LimitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.2...0.35 Uc 131 °F (55 °C))
- Tightening TorqueControl circuit 10.62 lbf.in (1.2 N.m) Power circuit 309.78 lbf.in (35 N.m)
- Contactor ApplicationMotor control Resistive load
- [Ui] Rated Insulation Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
- [Ue] Rated Operational Voltage<= 1000 V AC 50/60 Hz <= 460 V DC
- Mechanical Durability10 Mcycles
- Heat Dissipation6 W
- Hold-In Power Consumption In W6 W 68 °F (20 °C)
- Compatibility CodeLC1F
- Contactor Coil Voltage110 V DC standard
- Motor Starter TypeDirect on-line contactor
- Maximum Operating Rate2400 cyc/h 131 °F (55 °C)
- Inrush Power In W1000 W 68 °F (20 °C))
- Mounting SupportPlate
- [Ith] Conventional Free Air Thermal Current500 A 104 °F (40 °C)
- Overvoltage CategoryIII
- Rated Breaking Capacity3200 A IEC 60947-4-1
- [Uimp] Rated Impulse Withstand Voltage8 kV
- Coil TypeStandard
- Average Impedance0.26 mOhm - Ith 500 A 50 Hz
- Device Short NameLC1F
- RangeTeSys
- Poles Description3P
- [Uc] Control Circuit Voltage110 V DC
- Power Pole Contact Composition3 NO
- Product NameTeSys F
- Product Or Component TypeContactor
Get a quick quote
Select Qty:
Average response time:
11 minutes
This part can ship within 24h!
Fast worldwide Shipping and Delivery
Shipping cost will be calculated during checkout
Payments methods
Secure Payment Processing
with money back guarantee
1 year warranty on all parts
Responsive Customer Support
with personalized assistance
Need more details?
Feel free to chat with us.