LC1F500Q7
Schneider Electric
Product Lifecycle: Active
FR catalog.xlsx - SM-618
FR catalog.xlsx - SM-618
Product details
- Product CertificationsDNV CB RMRoS RINA CCC LROS (Lloyds register of shipping) BV ABS UL UKCA
- Motor Power Kw250 kW 380...400 V AC 50/60 Hz AC-3) 280 kW 415 V AC 50/60 Hz AC-3) 295 kW 440 V AC 50/60 Hz AC-3) 355 kW 500 V AC 50/60 Hz AC-3) 335 kW 660...690 V AC 50/60 Hz AC-3) 335 kW 1000 V AC 50/60 Hz AC-3) 147 kW 220...230 V AC 50/6
- StandardsEN 60947-4-1 IEC 60947-4-1 IEC 60947-1 JIS C8201-4-1 EN 60947-1
- [Icw] Rated Short-Time Withstand Current4200 A 104 °F (40 °C) - 10 s 3200 A 104 °F (40 °C) - 30 s 2400 A 104 °F (40 °C) - 1 min 1500 A 104 °F (40 °C) - 3 min 1200 A 104 °F (40 °C) - 10 min
- Utilisation CategoryAC-1 AC-3 AC-4
- Connections - TerminalsControl circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)fl
- [Ui] Rated Insulation Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
- [Ie] Rated Operational Current700 A 104 °F (40 °C)) <= 440 V AC AC-1 500 A 131 °F (55 °C)) <= 440 V AC AC-3
- Contactor ApplicationResistive load Motor control
- Control Circuit Voltage LimitsOperational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 40...400 Hz 131 °F (55 °C))
- Operating Time40...65 ms closing 100...170 ms opening
- [Ue] Rated Operational Voltage<= 1000 V AC 50/60 Hz <= 460 V DC
- Tightening TorqueControl circuit 10.62 lbf.in (1.2 N.m) Power circuit 309.78 lbf.in (35 N.m)
- Power Dissipation Per Pole88 W AC-1 45 W AC-3
- Associated Fuse Rating500 A aM <= 440 V 800 A gG <= 440 V
- Maximum Operating Rate2400 cyc/h 131 °F (55 °C)
- Compatibility CodeLC1F
- Mechanical Durability10 Mcycles
- Heat Dissipation18 W
- Hold-In Power Consumption In VA18 VA 40...400 Hz 0.9 68 °F (20 °C))
- Inrush Power In VA1100 VA 40...400 Hz 0.9 68 °F (20 °C))
- Mounting SupportPlate
- Average Impedance0.18 mOhm - Ith 700 A 50 Hz
- Overvoltage CategoryIII
- Rated Breaking Capacity4000 A IEC 60947-4-1
- [Ith] Conventional Free Air Thermal Current700 A 104 °F (40 °C)
- [Uimp] Rated Impulse Withstand Voltage8 kV
- [Uc] Control Circuit Voltage380 V AC 40...400 Hz
- Product Or Component TypeContactor
- Power Pole Contact Composition3 NO
- Poles Description3P
- Device Short NameLC1F
- RangeTeSys
- Product NameTeSys F
Get a quick quote
Select Qty:
Average response time:
11 minutes
This part can ship within 24h!
Fast worldwide Shipping and Delivery
Shipping cost will be calculated during checkout
Payments methods
Secure Payment Processing
with money back guarantee
1 year warranty on all parts
Responsive Customer Support
with personalized assistance
Need more details?
Feel free to chat with us.