RM22JA31MR
Schneider Electric
Product Lifecycle: Active
current control relay, Harmony Control Relays, 4mA…1 A, 2CO, 24…240V AC DC
current control relay, Harmony Control Relays, 4mA…1 A, 2CO, 24…240V AC DC
Product details
- Utilisation CategoryAC-15 IEC 60947-5-1 DC-13 IEC 60947-5-1 AC-1 IEC 60947-4-1 DC-1 IEC 60947-4-1
- Connections - TerminalsScrew terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end
- Measurement Range4...40 mA E1-M terminals 20...200 mA E2-M terminals 100...1000 mA E3-M terminals 4 mA...1 A current AC/DC 50/60 Hz
- Resistance Across Terminals2.5 Ohm E1-M terminals 0.5 Ohm E2-M terminals 0.1 Ohm E3-M terminals
- Internal Input Resistance0.5 Ohm 2.5 Ohm 0.1 Ohm
- Safety Reliability DataMTTFd = 296.8 years B10d = 270000
- Status LEDRelay ON LED Yellow) Power ON LED Green)
- Hysteresis5…50 % adjustable threshold setting overcurrent or undercurrent detection 3 % fixed full scale for window mode
- Repeat Accuracy+/- 0.5 % input and measurement circuit +/- 0.2 % time delay
- Overvoltage CategoryIII IEC 60664-1 III UL 508
- Switching Threshold Drift<= 0.05 % per degree centigrade depending permissible ambient air temperature <= 1 % within the supply voltage range
- Measurement Error< 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation
- Relay Monitored ParametersOvercurrent or undercurrent detection Overcurrent or undercurrent in window mode
- Time Delay Drift<= 0.05 % per degree centigrade depending permissible ambient air temperature <= 1 % within the supply voltage range
- Width0.89 in (22.5 mm)
- Net Weight0.24 lb(US) (0.11 kg)
- Contacts MaterialCadmium free
- Electrical Durability100000 cycles
- Housing MaterialSelf-extinguishing plastic
- Tightening Torque5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1
- Maximum Measuring Cycle100 ms measurement cycle as true rms value
- Response Time<= 500 ms
- Mechanical Durability10000000 cycles
- Mounting Support35 mm DIN rail conforming to EN/IEC 60715
- Mounting PositionAny position
- Insulation Resistance> 100 MOhm 500 V DC IEC 60255-27
- InsulationBetween supply and measurement
- Run-Up Delay At Power-Up0.3 s
- Threshold Setting10...100 %
- Setting Accuracy Of Time Delay10 P
- Setting Accuracy Of The Switching Threshold+/- 10 % of the full scale
- Nominal Output Current8 A
- Supply Voltage Frequency50...60 Hz +/- 10 %
- Output Contacts2 C/O
- Supply Voltage Limits20.4…264 V AC/DC
- [Us] Rated Supply Voltage24...240 V AC/DC 50/60 Hz +/- 10 %
- Reset Time1500 ms at maximum voltage
- Maximum Switching Current8 A AC
- Maximum Switching Voltage250 V AC
- Maximum Power Consumption In W1.5 W DC
- Power Consumption In VA3.5 VA AC
- Minimum Switching Current10 mA 5 V DC
- Operating Limits- 15 % + 10 % Un
- Contacts Type And Composition2 C/O
- Relay NameRM22JA
- Relay TypeCurrent control relay
- Switching Capacity In VA2000 VA
- Time Delay TypeAdjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
- Product Or Component TypeCurrent control relay
- Range Of ProductHarmony Control Relays
Get a quick quote
Select Qty:
Average response time:
11 minutes
This part can ship within 24h!
Fast worldwide Shipping and Delivery
Shipping cost will be calculated during checkout
Payments methods
Secure Payment Processing
with money back guarantee
1 year warranty on all parts
Responsive Customer Support
with personalized assistance
Need more details?
Feel free to chat with us.