RM22UA32MR

Schneider Electric

Product Lifecycle: Active

voltage control relay, Harmony Control Relays, 8A, 2CO, overvoltage or undervoltage detection, 1…100V AC DC, 24…240V AC DC

RM22UA32MR

voltage control relay, Harmony Control Relays, 8A, 2CO, overvoltage or undervoltage detection, 1…100V AC DC, 24…240V AC DC

  • Connections - TerminalsScrew terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end
  • Utilisation CategoryAC-15 IEC 60947-5-1 DC-13 IEC 60947-5-1 AC-1 IEC 60947-4-1 DC-1 IEC 60947-4-1
  • Resistance Across Terminals110 kOhm E2-M terminals 22 kOhm E1-M terminals 220 kOhm E3-M terminals
  • Repeat Accuracy+/- 0.5 % input and measurement circuit +/- 2 % time delay
  • Relay Monitored ParametersUndervoltage and overvoltage in window mode Overvoltage or undervoltage detection
  • Safety Reliability DataB10d = 290000 MTTFd = 308.2 years
  • Measurement Error< 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation
  • Hysteresis3 % fixed full scale for window mode 5…50 % adjustable threshold setting overvoltage or undervoltage detection
  • Status LEDRelay ON LED Yellow) Power ON LED Green)
  • Housing MaterialSelf-extinguishing plastic
  • Width0.89 in (22.5 mm)
  • Net Weight0.24 lb(US) (0.11 kg)
  • Mechanical Durability10000000 cycles
  • Electrical Durability100000 cycles
  • Contacts MaterialCadmium free
  • Mounting Support35 mm DIN rail conforming to EN/IEC 60715
  • Mounting PositionAny position
  • Tightening Torque5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1
  • InsulationBetween supply and measurement
  • Insulation Resistance> 100 MOhm 500 V DC IEC 60255-27
  • Maximum Measuring Cycle100 ms measurement cycle as true rms value
  • Overvoltage CategoryIII IEC 60664-1
  • Response Time<= 500 ms
  • Run-Up Delay At Power-Up600 ms
  • Output Contacts2 C/O
  • Nominal Output Current8 A
  • Maximum Power Consumption In W1.5 W DC
  • Supply Voltage Frequency40...70 Hz +/- 10 %
  • Supply Voltage Limits20.4…264 V AC/DC
  • [Us] Rated Supply Voltage24...240 V AC/DC 50/60 Hz
  • Power Consumption In VA3.5 VA AC
  • Maximum Switching Current8 A AC
  • Minimum Switching Current10 mA 5 V DC
  • Contacts Type And Composition2 C/O
  • Maximum Switching Voltage250 V AC
  • Reset Time1500 ms at maximum voltage
  • Measurement Range1...100 V voltage AC/DC 50/60 Hz
  • Relay TypeVoltage control relay
  • Supply Circuit TypeDC
  • Range Of ProductHarmony Control Relays
  • Relay NameRM22UA
  • Product Or Component TypeVoltage control relay
  • Time Delay TypeAdjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
  • Switching Capacity In VA2000 VA
  • Phase1 phase

Get a quick quote

Select Qty:

Average response time:

11 minutes

This part can ship within 24h!

Fast worldwide Shipping and Delivery

Shipping cost will be calculated during checkout


Payments methods

Secure Payment Processing
with money back guarantee

1 year warranty on all parts


Responsive Customer Support
with personalized assistance


Need more details?

Feel free to chat with us.

Friendly Powermatic robot

What can I help you find today?