LC1F630U7
Schneider Electric
Product Lifecycle: Active
CONTACTOR 600VAC 630AMP IEC +OPTIONS
CONTACTOR 600VAC 630AMP IEC +OPTIONS
Product details
- Product CertificationsUL LROS (Lloyds register of shipping) ABS RINA RMRoS CSA DNV CB BV UKCA
- StandardsEN 60947-4-1 EN 60947-1 IEC 60947-4-1 JIS C8201-4-1 IEC 60947-1
- [Icw] Rated Short-Time Withstand Current5050 A 104 °F (40 °C) - 10 s 4400 A 104 °F (40 °C) - 30 s 3400 A 104 °F (40 °C) - 1 min 2200 A 104 °F (40 °C) - 3 min 1600 A 104 °F (40 °C) - 10 min
- Motor Power Kw335 kW 380...400 V AC 50/60 Hz AC-3) 375 kW 415 V AC 50/60 Hz AC-3) 400 kW 440 V AC 50/60 Hz AC-3) 400 kW 500 V AC 50/60 Hz AC-3) 450 kW 660...690 V AC 50/60 Hz AC-3) 450 kW 1000 V AC 50/60 Hz AC-3) 200 kW 220...230 V AC 50/6
- Motor Power Range250…500 kW 380…440 V 3 phase 110…220 kW 200…240 V 3 phase 250…500 kW 480…500 V 3 phase
- Connections - TerminalsControl circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)fl
- Utilisation CategoryAC-1 AC-4 AC-3
- Power Dissipation Per Pole120 W AC-1 48 W AC-3
- Associated Fuse Rating1000 A gG <= 440 V 630 A aM <= 440 V
- Control Circuit Voltage LimitsOperational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.25...0.5 Uc 40...400 Hz 131 °F (55 °C))
- Contactor ApplicationMotor control Resistive load
- [Ui] Rated Insulation Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
- [Ie] Rated Operational Current1000 A 104 °F (40 °C)) <= 440 V AC AC-1 630 A 131 °F (55 °C)) <= 440 V AC AC-3
- [Ue] Rated Operational Voltage<= 1000 V AC 50/60 Hz <= 460 V DC
- [Ith] Conventional Free Air Thermal Current1000 A 104 °F (40 °C) 1250 A
- Tightening TorqueControl circuit 10.62 lbf.in (1.2 N.m) Power circuit 513.34 lbf.in (58 N.m)
- Operating Time40...80 ms closing 100...200 ms opening
- Contactor Coil Voltage240 V AC standard
- Motor Starter TypeDirect on-line contactor
- Maximum Operating Rate1200 cyc/h 131 °F (55 °C)
- Compatibility CodeLC1F
- Mechanical Durability5 Mcycles
- Heat Dissipation20 W
- Hold-In Power Consumption In VA22 VA 40...400 Hz 0.9 68 °F (20 °C))
- Inrush Power In VA1650 VA 40...400 Hz 0.9 68 °F (20 °C))
- Average Impedance0.12 mOhm - Ith 1000 A 50 Hz
- Mounting SupportPlate
- Rated Breaking Capacity5040 A IEC 60947-4-1
- Overvoltage CategoryIII
- [Uc] Control Circuit Voltage240 V AC 40...400 Hz
- [Uimp] Rated Impulse Withstand Voltage8 kV
- Poles Description3P
- Power Pole Contact Composition3 NO
- Device Short NameLC1F
- Product Or Component TypeContactor
- RangeTeSys
- Product NameTeSys F
$6,474.00
Select Qty:
$6,474.00
$6,474.00 each
Average response time:
11 minutes
This part can ship within 24h!
Fast worldwide Shipping and Delivery
Shipping cost will be calculated during checkout
Payments methods
Secure Payment Processing
with money back guarantee
1 year warranty on all parts
Responsive Customer Support
with personalized assistance
Need more details?
Feel free to chat with us.